CSX Compact Low Voltage Soft Starter

Image

EMX3 Low Voltage Soft Starter

Compact size

The CSX is a compact and lightweight unit, so it is suitable for installation in small spaces and is the ideal replacement for older starters.

Easy-to-use adjustments

The CSX is easy to configure, with three simple adjustments. Select the initial start voltage, start ramp time and stop ramp time (if required), and the starter is ready to go. Rotary dials allow reliable, repeatable confguration with no need to navigate through a menu and no difficult-to-use dip switches.

Integrated bypass contactors

Integrated bypass contactors simplify installation by reducing the need to select and connect additional equipment. Because the contactors are already contained within the starter, the overall size of the installation is also smaller. Bypassing the starter while the motor is running reduces the amount of heating, so the starter can usually be installed with no additional ventilation.

Communications

CSXi soft starters integrate into your existing DeviceNet, Modbus, Profibus or Ethernet network using easy-to-install plug-in communication interfaces. The optional remote operator can be installed to provide remote feedback, including current, temperature and starter status.

Finger Guards

For enhanced personnel safety and protection, AuCom has developed insulating finger guards, which install quickly and easily onto 75 kW ~ 110 kW CSX Series units to provide IP20 protection.

Mains Supply

      
Mains voltage (L1, L2, L3)    
CSX-xxx-V4   3 x 200 VAC ~ 440 VAC (+ 10% / - 15%)
CSX-xxx-V6   3 x 200 VAC ~ 575 VAC (+ 10% / - 15%)
Mains frequency (at start)   45 Hz to 66 Hz
Rated insulation voltage   600 VAC
Form designation   Bypassed semiconductor motor starter form 1
Control Voltage (A1, A2, A3)    
CSX-xxx-xx-C1   110-240 VAC (+ 10% / - 15%)
    or 380-440 VAC (+ 10% / - 15%)
CSX-xxx-xx-C2   24 VAC/VDC (± 20%)
Current consumption (during run)   < 100 mA
Current consumption (at power-up)    
CSX-xxx-xx-C1   10 A
CSX-xxx-xx-C2   2 A


Inputs

   
Start (terminal 01)   Normally Open
    150 kΩ @ 300 VAC and 5.6 kΩ @ 24 VAC/VDC
Stop (terminal 02)   Normally Closed
    150 kΩ @ 300 VAC and 5.6 kΩ @ 24 VAC/VDC


Outputs

   
Main contactor (terminals 13, 14)   Normally Open
    6 A, 30 VDC / 6 A, 250 VAC resistive
Programmable relay (terminals 23, 24)   Normally Open
    6 A, 30 VDC / 6 A, 250 VAC resistive


Environmental

   
Degree of protection CSX-007 to CSX-055   IP20
Degree of protection CSX-075 to CSX-110   IP00
Operating temperatures   - 10 °C to + 60 °C
Humidity   5% to 95% Relative Humidity
Pollution degree   Pollution Degree 3
Vibration   IEC 60068 Test Fc Sinusoidal
    4 Hz to 13.2 Hz: ± 1 mm displacement
    13.2 Hz to 200 Hz: ± 0.7 g


EMC Emission

   
Equipment class (EMC)   Class B
Conducted radio frequency emission   0.15 MHz to 0.5 MHz: < 56-46 dB (µV)
    0.5 MHz to 5 MHz: < 46 dB (µV)
    5 MHz to 30 MHz: 50 dB (µV)
Radiated radio frequency emission   30 MHz to 230 MHz: < 30 dB (µV/m)
    230 MHz to 1000 MHz: < 37 dB (µV/m)
     
This product has been designed as Class A equipment. Use of this product in domestic environments may cause radio interference, in which case the user may be required to employ additional mitigation methods.


EMC Immunity

   
Electrostatic discharge   4 kV contact discharge, 8 kV air discharge
Radio frequency electromagnetic field   0.15 MHz to 1000 MHz: 140 dB (µV)
Rated impulse withstand voltage (Fast transients 5/50 ns)   2 kV line to earth, 1 kV line to line
Voltage dip and short time interruption   100 ms (at 40% nominal voltage)
Harmonics and distortion   IEC61000-2-4 (Class 3), EN/IEC61800-3


Short Circuit

   
Rated short-circuit current CSX-007 to CSX-037   5 kA
Rated short-circuit current CSX-045 to CSX-110   10 kA


Heat Dissipation

   
During Start   3 watts / ampere
During Run   10 watts typical


Approvals

   
RCM   IEC 60947-4-2
CE   EN 60947-4-2
CCC   GB 14048.6
EAC   TP TC 004/2011, TP TC 020/2011
Marine   Lloyds Marine No 1 Specification
UL / C-UL   UL 508
 

Contact Us

Email: info@younes.com.jo

Fax: +962 6 4207787

Phone: +962 6 4207783

Address: Abu Bakr Al-Aajeri St, Amman, Jordan

Social Media

Search